Prefabricated Chambers of Unilateral Service PCUS-393-M - Nika Energy

Prefabricated Chambers of Unilateral Service PCUS-393-M

Prefabricated Chambers of Unilateral Service PCUS-393 and bus bridges are installed in switchgear assemblies with a rated voltage of 10 (6) kV and are designed for the distribution of 50 Hz alternating current electrical power.

Conclusions and Certificates (click here)

price on request

Legend

PCUS-393-XX-XX/XX-U3
hover over the mark to see the transcript
Description
Schemes / Drawings
Specifications

The list of Prefabricated Chambers of Unilateral Service (PCUS), bus bridges, circuit diagrams, and brief technical characteristics is provided in Table 1.

The general arrangement and overall dimensions are shown in Figure 1.

Climatic version: U3 in accordance with GOST 15150.

Degree of protection in accordance with GOST 14254:

  • IP30 — for the front side of the enclosure (with the doors closed) and the side walls of the chambers.
  • IP00 — for the remaining chamber sections.

The switchgear assembly complies with TU U 27.1-45149048-002:2024.

To order a Prefabricated Chamber of Unilateral Service (PCUS), a completed technical questionnaire specifying the required equipment parameters must be submitted.

Diagram 1
Diagram 1
Parameter Value
Rated voltage (line-to-line), kV 6; 10
Maximum operating voltage, kV 7.2; 12
Rated power supply frequency, Hz 50
* Rated current of main circuits, A:
- busbars 630
- chambers with load-break switches 630
- chambers with disconnectors 630
- chambers with fuses see below
- bus bridges 630
* Fuse-link rated current, A:
at Un = 6 kV 31.5; 50; 80; 100; 125
at Un = 10 kV 31.5; 40; 63; 80; 100
Electrodynamic withstand of main circuits, kA 41
Thermal withstand of main circuits, kA 16
Table 1.1 Technical Specifications

Note: * the rated current of the chamber or bus bridge corresponds to the rated current of the incoming device or the rated current of the fuse link.

Name and Type Application Electrical Parameters Weight, kg
U, kV I, A
PCUS-393-M Line chamber with disconnector 10 630 140

Table 1.2 Chamber Types

Chamber Type Single-Line Diagram Type of Main Device
PCUS-393-M Diagram 1 VVNA-Pp-10/630; PT; OPNp-10
Table 1.3 Single-Line Electrical Diagrams

Associated products