Block-Type Compact Transformer Substations (BTCTS) - Nika Energy

Block-Type Compact Transformer Substations (BTCTS)

Block-Type Compact Transformer Substations (BTCTS) are technical installations with the following specifications: rated power from 100 to 2,500 kVA, designed for networks with an isolated or compensated neutral on the 6 (10) kV side and a solidly grounded neutral on the 0.4 kV side.

price on request

Legend

BTCTS-X-X-X-XX
hover over the mark to see the transcript
Description
Schemes / Drawings
Specifications

Block-Type Compact Transformer Substations (BTCTS) feature a distinctive block-based design that integrates transformers and switchgear into modular units.

They are designed to receive, transform, and distribute electrical power in low-voltage networks, providing reliable and efficient power supply to a wide range of consumers.

BTCTS reduce installation time and simplify operation thanks to their modular design, making them particularly popular among engineers and companies in the power industry.

Key Advantages and Features of BTCTS:

  • Modularity: BTCTS consist of modular units, reducing installation time and simplifying operation and maintenance.
  • Reliability: Integrated transformers and switchgear ensure stable and uninterrupted power supply to consumers.
  • Efficiency: BTCTS optimize energy efficiency and reduce power losses through their design.
  • Versatility: They are suitable for use in a wide range of conditions and environments, making them adaptable to various power infrastructure projects.
  • Space Saving: The compact design of BTCTS enables efficient use of limited space and facilitates installation where available space is restricted.

Nika Energy manufactures Block-Type Compact Transformer Substations (BTCTS) in both standard configurations and customized designs according to customer requirements. To receive an assessment, please attach your project to your inquiry.

ParameterValue
Rated voltage on the HV side, kV6; 10
Rated voltage on the LV side, kV0.4
Maximum voltage on the HV side, kV7.2; 12
Rated busbar current on the HV side, A400; 630
Rated busbar current on the LV side, A630; 1000; 1600; 2000
Rated current of outgoing LV switchgear feeders, A2000
Rated frequency, Hz50
Insulation level according to GOST 1516.1-76Normal
Degree of protection of the built-in equipment provided by the enclosure according to GOST 22789-94IP 23
Table 1 Main Technical Specifications of BTCTS